Unit of Competency Mapping – Information for Teachers/Assessors – Information for Learners

UEENEEH061B Mapping and Delivery Guide
Position and terminate fire detection and warning system apparatus

Version 1.0
Issue Date: April 2024


Qualification -
Unit of Competency UEENEEH061B - Position and terminate fire detection and warning system apparatus
Description 1)1.1) This unit covers installing electronic fire detection and warning systems in buildings and premises. It encompasses, working safely and to standards, following oral and written instructions and procedures, securely placing and connecting fire detection system and warning, components, and applying customer relation protocols.
Employability Skills 3)This unit contains Employability SkillsThe required outcomes described in this unit of competency contain applicable facets of Employability Skills. The Employability Skills Summary of the qualification in which this unit of competency is packaged will assist in identifying Employability Skill requirements.
Learning Outcomes and Application 4) The skills and knowledge described in this unit require a license to practice in the workplace where plant and equipment operate at voltage above 50 V a.c. or 120 V d.c. However other conditions may apply in some States/Territories subject to regulations related to electrical work. Where the fire alarm system has a call-back-to-base facility practice in the workplace is also subject to ACMA regulations to undertake cabling work.Note:Unit 'UEENEEF002B' provides the required skill and knowledge for registration in accordance with ACMA regulations for undertaking cabling workPractice in the workplace and during training is also subject to regulations directly related to occupational health and safety and where applicable contracts of training such as apprenticeships.
Duration and Setting X weeks, nominally xx hours, delivered in a classroom/online/blended learning setting.
Prerequisites/co-requisites Prerequisite Unit(s) 2) 2.1) CompetenciesGranting competency in this unit shall be made only after competency in the following unit(s) has/have been confirmed.UEENEEE002B Dismantle, assemble and fabricate electrotechnology componentsUEENEEE005B Fix and secure equipmentUEENEEE007B Use drawings, diagrams, schedules and manualsFor the full prerequisite chain details for this unit please refer to Table 2 in Volume 1, Part 2
Competency Field
Development and validation strategy and guide for assessors and learners Student Learning Resources Handouts
Activities
Slides
PPT
Assessment 1 Assessment 2 Assessment 3 Assessment 4
Elements of Competency Performance Criteria              
Element: Prepare to assemble and set up basic fire detection and warning systems.
  • OHS procedures for a given work area are identified, obtained and understood through established routines.
  • Established OHS risk control measures are followed in preparation for the work.
  • Safety hazards that have not previously been identified are reported and advise on risk control measures are sought from the work supervisor.
  • The nature and location of the work is obtained from work supervisor or other appropriate person to establish the scope of work to be undertaken.
  • Advice is sought from the work supervisor or other appropriate person to ensure the work is co-ordinated effectively with others.
  • Sources of materials that may be required for the work are established in accordance with established routines.
  • Tools, equipment and testing devices needed to carry out the work are obtained and checked for correct operation and safety.
       
Element: Assemble and set up basic fire detection and warning systems.
  • Established OHS risk control measures for carrying out the work are followed.
  • Circuits/machines/plant are checked as being isolated where necessary in strict accordance OHS requirements and procedures.
  • Fire protection controller and detection and warning devices are located for optimum performance within limitation imposed by customers and regulations.
  • Accessories are installed straight and square in the required locations and within acceptable tolerances.
  • Cables and conductors are terminated at accessories in accordance with manufacture's specifications and regulatory requirements.
  • Procedures for referring non-routine events to immediate supervisor for directions are followed.
  • Fire protection installation is carried out efficiently without waste of materials or damage to apparatus, circuits or the surrounding environment and using sustainable energy practices.
       
Element: Set up basic fire detection and warning systems.
  • OHS work completion risk control measures and procedures are followed.
  • Work site is cleaned and made safe in accordance with established procedures.
  • Fire protection system is documented in accordance with regulatory requirement and established routines.
       


Evidence Required

List the assessment methods to be used and the context and resources required for assessment. Copy and paste the relevant sections from the evidence guide below and then re-write these in plain English.

9) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package. .

The Evidence Guide forms an integral part of this unit. It must be used in conjunction with all parts of the unit and performed in accordance with the Assessment Guidelines of this Training Package.

Overview of Assessment

9.1)

Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the Industry-preferred model for apprenticeships. However, where summative (or final) assessment is used it must include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. It is recognised that, in some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accord with industry and regulatory policy.

Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed.

The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment.

Activities associated with normal everyday work influence decisions about how/how much the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package.

Critical aspects of evidence required to demonstrate competency in this unit

9.2)

Before the critical aspects of evidence are considered all prerequisites shall be met.

Evidence for competence in this unit shall be considered holistically. Each Element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:

A representative body of work performance demonstrated within the timeframes typically expected of the discipline, work function and industrial environment. In particular this shall incorporate evidence that shows a candidate is able to:

Implement Occupational Health and Safety workplace procedures and practices, including the use of risk control measures as specified in the performance criteria and range statement

Apply sustainable energy principles and practices as specified in the performance criteria and range statement

Demonstrate an understanding of the essential knowledge and associated skills as described in this unit. It may be required by some jurisdictions that RTOs provide a percentile graded result for the purpose of regulatory or licensing requirements.

Demonstrate an appropriate level of skills enabling employment

Conduct work observing the relevant Anti Discrimination legislation, regulations, polices and workplace procedures

Demonstrated consistent performance across a representative range of contexts from the prescribed items below:

Position and terminate fire detection and warning system apparatus as described in 8) and including:

A

Reading and interpreting drawings showing apparatus/device locations and connection arrangements.

B

Placing and securing devices and accessories accurately.

C

Maintaining fire integrity.

D

Terminating cable and conductors correctly.

E

Documenting installation.

F

Dealing with unplanned events by drawing on essential knowledge and skills to provide appropriate solutions incorporated in a holistic assessment with the above listed items.

Note:
Successful completion of relevant vendor training may be used to contribute to evidence on which competency is deemed. In these cases the alignment of outcomes of vendor training with performance criteria and critical aspects of evidence shall be clearly identified.

Context of and specific resources for assessment

9.3)

This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:

OHS policy and work procedures and instructions.

Suitable work environment, facilities, equipment and materials to undertake actual work as prescribed by this unit.

These should be part of the formal learning/assessment environment.

Note:

Where simulation is considered a suitable strategy for assessment, conditions must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy.

The resources used for assessment should reflect current industry practices in relation to positioning and terminating fire detection and warning system apparatus.

Method of assessment

9.4)

This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'.

Note:
Competent performance with inherent safe working practices is expected in the industry to which this unit applies. This requires that the specified essential knowledge and associated skills are assessed in a structured environment which is primarily intended for learning/assessment and incorporates all necessary equipment and facilities for learners to develop and demonstrate the essential knowledge and skills described in this unit.

Concurrent assessment and relationship with other units

9.5)

For optimisation of training and assessment effort, competency development in this unit may be arranged concurrently with unit:

UEENEEE002B

Dismantle, assemble and fabricate electrotechnology components

UEENEEE005B

Fix and secure equipment

UEENEEE007B

Use drawings, diagrams, schedules and manuals

UEENEEE008B

Lay wiring/cabling and terminate accessories for extra-low voltage circuits

UEENEEF016A

Install and maintain cabling for direct access to telecommunication services


Submission Requirements

List each assessment task's title, type (eg project, observation/demonstration, essay, assignment, checklist) and due date here

Assessment task 1: [title]      Due date:

(add new lines for each of the assessment tasks)


Assessment Tasks

Copy and paste from the following data to produce each assessment task. Write these in plain English and spell out how, when and where the task is to be carried out, under what conditions, and what resources are needed. Include guidelines about how well the candidate has to perform a task for it to be judged satisfactory.

7) This describes the essential skills and knowledge and their level, required for this unit.

Evidence shall show that knowledge has been acquired of safe working practices and positioning and terminating fire detection and warning system apparatus.

All knowledge and skills detailed in this unit should be contextualised to current industry practices and technologies.

The extent of the essential knowledge and associated skills (EKAS) required is given in Volume 2 - Part 2.2 EKAS. It forms an integral part of this unit.

2.5.21

Technical standards, regulations and codes for fire protection and warning systems

2.9.36

Fire detection and warning system and apparatus fundamentals

2.9.79.1

Fire protection technologies

2.18.11

Fire protection equipment safe working practices

8) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance.

This unit shall be demonstrated using a representative range of fire detection and warning system apparatus by installing at least two-fire alarm and warning systems.

Installation shall include the following system components:

Fire alarm system with at least one Control&Indicating panel, 50 input devices, 5 output device and 2 system interface controls on at least of the following: Analogue addressable system, addressable system and or conventional system.

Fire warning system with at least one Control&Indicating panel, 50 speakers, 5 interface communication devices and 2 warning indicators

Note:
1. Input devices can be conventional, analogue or analogue addressable fire detectors, flow switch connections or switch connections and the like.
2. Output devices can be shutdown signal, door or system release controls, solenoid valve controls and the like.
3. System interface controls can be communication signals to remote Control and indicating equipment, Building monitoring systems, paging system, Colour graphics and or the like.
4. Interface communication devices can be Warden Incommunication phones, Remote PA inputs and the like.
5. Warning Indicators are flashing lights for hearing impaired persons, fire brigade building indication and the like.

Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1.

Copy and paste from the following performance criteria to create an observation checklist for each task. When you have finished writing your assessment tool every one of these must have been addressed, preferably several times in a variety of contexts. To ensure this occurs download the assessment matrix for the unit; enter each assessment task as a column header and place check marks against each performance criteria that task addresses.

Observation Checklist

Tasks to be observed according to workplace/college/TAFE policy and procedures, relevant legislation and Codes of Practice Yes No Comments/feedback
OHS procedures for a given work area are identified, obtained and understood through established routines. 
Established OHS risk control measures are followed in preparation for the work. 
Safety hazards that have not previously been identified are reported and advise on risk control measures are sought from the work supervisor. 
The nature and location of the work is obtained from work supervisor or other appropriate person to establish the scope of work to be undertaken. 
Advice is sought from the work supervisor or other appropriate person to ensure the work is co-ordinated effectively with others. 
Sources of materials that may be required for the work are established in accordance with established routines. 
Tools, equipment and testing devices needed to carry out the work are obtained and checked for correct operation and safety. 
Established OHS risk control measures for carrying out the work are followed. 
Circuits/machines/plant are checked as being isolated where necessary in strict accordance OHS requirements and procedures. 
Fire protection controller and detection and warning devices are located for optimum performance within limitation imposed by customers and regulations. 
Accessories are installed straight and square in the required locations and within acceptable tolerances. 
Cables and conductors are terminated at accessories in accordance with manufacture's specifications and regulatory requirements. 
Procedures for referring non-routine events to immediate supervisor for directions are followed. 
Fire protection installation is carried out efficiently without waste of materials or damage to apparatus, circuits or the surrounding environment and using sustainable energy practices. 
OHS work completion risk control measures and procedures are followed. 
Work site is cleaned and made safe in accordance with established procedures. 
Fire protection system is documented in accordance with regulatory requirement and established routines. 

Forms

Assessment Cover Sheet

UEENEEH061B - Position and terminate fire detection and warning system apparatus
Assessment task 1: [title]

Student name:

Student ID:

I declare that the assessment tasks submitted for this unit are my own work.

Student signature:

Result: Competent Not yet competent

Feedback to student

 

 

 

 

 

 

 

 

Assessor name:

Signature:

Date:


Assessment Record Sheet

UEENEEH061B - Position and terminate fire detection and warning system apparatus

Student name:

Student ID:

Assessment task 1: [title] Result: Competent Not yet competent

(add lines for each task)

Feedback to student:

 

 

 

 

 

 

 

 

Overall assessment result: Competent Not yet competent

Assessor name:

Signature:

Date:

Student signature:

Date: