The important thing to remember when gathering evidence is that the more evidence the better - that is, the more evidence you gather to demonstrate your skills, the more confident an assessor can be that you have learned the skills not just at one point in time, but are continuing to apply and develop those skills (as opposed to just learning for the test!). Furthermore, one piece of evidence that you collect will not usualy demonstrate all the required criteria for a unit of competency, whereas multiple overlapping pieces of evidence will usually do the trick!

From the Wiki University

 

MEM18084A - Commission and decommission split air conditioning systems

What evidence can you provide to prove your understanding of each of the following citeria?

Determine the operating conditions of vapour compression systems

  1. Established procedures are used to determine the actual and specified range of operating conditions from measured and calculated values as they apply to particular vapour compression systems.
  2. Established OHS procedures and risk control measures for carrying out the work are followed.
  3. Operating conditions are established and recorded on commissioning documentation.
  4. Tools, equipment and testing devices needed to determine the basic operating conditions are obtained and checked for correct operation and safety
  5. The system is checked and isolated where necessary, in strict accordance OHS requirements and procedures
Established procedures are used to determine the actual and specified range of operating conditions from measured and calculated values as they apply to particular vapour compression systems.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Established OHS procedures and risk control measures for carrying out the work are followed.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Operating conditions are established and recorded on commissioning documentation.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Tools, equipment and testing devices needed to determine the basic operating conditions are obtained and checked for correct operation and safety

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The system is checked and isolated where necessary, in strict accordance OHS requirements and procedures

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Recover refrigerants from split air conditioning systems

  1. Circuits/appliances are isolated where necessary in strict accordance OHS requirements and procedures.
  2. Refrigerants are removed safely into suitably labelled containers in accordance with legislative and industry requirements.
  3. Contaminated refrigerant is dealt with in accordance with legislative and industry requirements.
Circuits/appliances are isolated where necessary in strict accordance OHS requirements and procedures.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Refrigerants are removed safely into suitably labelled containers in accordance with legislative and industry requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Contaminated refrigerant is dealt with in accordance with legislative and industry requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Pressure and leak test split air conditioning systems

  1. Safety hazards are identified and noted and established risk control measures are implemented.
  2. Industry codes of practice and manufacturer installation instructions are followed.
  3. Precautions are taken to prevent damage to components while pressure testing the system.
  4. Pressure testing is conducted at a pressure compatible with the refrigerant to be used.
  5. Leaks are located, isolated and repaired using methods appropriate to the system type under test and in accordance with industry practices.
Safety hazards are identified and noted and established risk control measures are implemented.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Industry codes of practice and manufacturer installation instructions are followed.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Precautions are taken to prevent damage to components while pressure testing the system.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Pressure testing is conducted at a pressure compatible with the refrigerant to be used.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Leaks are located, isolated and repaired using methods appropriate to the system type under test and in accordance with industry practices.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Evacuate split air conditioning systems

  1. Safety hazards which have not previously been identified are noted, and established risk control measures are implemented.
  2. The system is evacuated to the required level and cleaned the system of all moisture and other containments in accordance with legislative and industry requirements.
  3. A standing vacuum test is applied in accordance with industry codes of practice and applicable standards.
Safety hazards which have not previously been identified are noted, and established risk control measures are implemented.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The system is evacuated to the required level and cleaned the system of all moisture and other containments in accordance with legislative and industry requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

A standing vacuum test is applied in accordance with industry codes of practice and applicable standards.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Charge split air conditioning systems

  1. Correct refrigerant is selected for the system, in accordance with manufacturer requirements and industry practices.
  2. The refrigerant charge is measured by weight in accordance with manufacturer specifications.
  3. The system is charged correctly in accordance with manufacturer requirements and industry practices.
  4. All components are checked and maintained in accordance with manufacturer requirements.
Correct refrigerant is selected for the system, in accordance with manufacturer requirements and industry practices.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The refrigerant charge is measured by weight in accordance with manufacturer specifications.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The system is charged correctly in accordance with manufacturer requirements and industry practices.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

All components are checked and maintained in accordance with manufacturer requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Test the operation of split air conditioning systems

  1. The system is started and operated in accordance with manufacturer instructions
  2. Standard tests are carried out to confirm system performance to manufacturer specifications.
  3. The refrigerant charge is checked and refrigerant added if required.
  4. The system is leak checked in accordance with refrigeration procedures and practices.
  5. Test data is recorded as required.
The system is started and operated in accordance with manufacturer instructions

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Standard tests are carried out to confirm system performance to manufacturer specifications.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The refrigerant charge is checked and refrigerant added if required.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The system is leak checked in accordance with refrigeration procedures and practices.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Test data is recorded as required.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Complete the commissioning/recommissioning of split air conditioning systems

  1. The worksite is cleaned and left in presentable condition in accordance with original presentation, client requirements, industry standards and organisational requirements.
  2. Final inspections are undertaken to ensure installation conforms with industry, legislative and work order requirements.
  3. The client is instructed on the use of the product in accordance with organisational requirements and manufacturer specifications.
  4. Certificates of compliance and other relevant commissioning documentation are completed and processed in accordance with State regulatory requirements.
The worksite is cleaned and left in presentable condition in accordance with original presentation, client requirements, industry standards and organisational requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Final inspections are undertaken to ensure installation conforms with industry, legislative and work order requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The client is instructed on the use of the product in accordance with organisational requirements and manufacturer specifications.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Certificates of compliance and other relevant commissioning documentation are completed and processed in accordance with State regulatory requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Decommission split air conditioning systems

  1. Plug in appliance is electrically disconnected or arrangements made for appropriately licensed person to isolate hard-wired appliances
  2. Refrigerants are recovered, stored and disposed of in accordance with legislative and industry requirements.
  3. Units and components are removed and disposed of safely and in accordance with regulations, industry codes of practice and sustainable environmental practices.
  4. The worksite is cleaned and left in presentable condition, client and organisational requirements, industry standards and sustainable environmental practices.
  5. Decommissioning documentation is completed and processed in accordance with State regulatory requirements.
Plug in appliance is electrically disconnected or arrangements made for appropriately licensed person to isolate hard-wired appliances

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Refrigerants are recovered, stored and disposed of in accordance with legislative and industry requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Units and components are removed and disposed of safely and in accordance with regulations, industry codes of practice and sustainable environmental practices.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

The worksite is cleaned and left in presentable condition, client and organisational requirements, industry standards and sustainable environmental practices.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Decommissioning documentation is completed and processed in accordance with State regulatory requirements.

Completed
Date:

Teacher:
Evidence:

 

 

 

 

 

 

 

Assessed

Teacher: ___________________________________ Date: _________

Signature: ________________________________________________

Comments:

 

 

 

 

 

 

 

 

Instructions to Assessors

Evidence Guide

The evidence guide provides advice on assessment and must be read in conjunction with the performance criteria, required skills and knowledge, range statement and the Assessment Guidelines for the Training Package.

Overview of assessment

A person who demonstrates competency in this unit must be able to install split air conditioning systems to manufacturer specifications, safely, to relevant Australian Standards, codes and regulations.

Competency in this unit cannot be claimed until all prerequisites have been satisfied.

Critical aspects for assessment and evidence required to demonstrate competency in this unit

Assessors must be satisfied that the candidate can competently and consistently perform all elements of the unit as specified by the criteria, including required knowledge, and be capable of applying the competency in new and different situations and contexts.

Context of and specific resources for assessment

This unit may be assessed on the job, off the job or a combination of both on and off the job. Where assessment occurs off the job, that is the candidate is not in productive work, then an appropriate simulation must be used where the range of conditions reflects realistic workplace situations. The competencies covered by this unit would be demonstrated by an individual working alone or as part of a team. The assessment environment should not disadvantage the candidate.

This unit could be assessed in conjunction with any other units addressing the safety, quality, communication, materials handling, recording and reporting associated with commissioning, recommissioning and decommissioning split air conditioning systems or domestic air conditioning and refrigeration appliances and other units requiring the exercise of the skills and knowledge covered by this unit.

Method of assessment

Assessors should gather a range of evidence that is valid, sufficient, current and authentic. Evidence can be gathered through a variety of ways including direct observation, supervisor reports, project work, samples and questioning. Questioning techniques should not require language, literacy and numeracy skills beyond those required in this unit of competency. The candidate must have access to all tools, equipment, materials and documentation required. The candidate must be permitted to refer to any relevant workplace procedures, product and manufacturing specifications, codes, standards, manuals and reference materials.

Guidance information for assessment

Required Skills and Knowledge

Required skills

Look for evidence that confirms skills in:

reading, interpreting and following information on written job instructions, specifications, standard operating procedures, charts, catalogues, lists, drawings and other applicable reference documents

effective communication with appropriate persons

planning and sequencing operations

checking and clarifying task related information

using tools, techniques and equipment necessary to check for correct operation

comparing system and component performance/ operation against specification

identifying faulty components and non-compliances

using appropriate test equipment to identify non-compliance

safely removing, containing and adding refrigerant to relevant Australian Standards or codes and regulations

making required adjustments to achieve specifications

applying safety procedures, standard operating procedures and legislative requirements to all work undertaken

completing relevant commissioning and decommissioning documentation

Required knowledge

Look for evidence that confirms knowledge of:

applicable legislative and regulatory requirements, standards, codes, licensing requirements and sustainable environmental practices for commissioning and decommissioning systems

applicable procedures and legislative requirements for storage, handling and treatment of ozone depleting and synthetic greenhouse gas refrigerant

procedures to determine the actual and specified range of operating conditions from measured and calculated values as they apply to particular vapour compression systems

typical work environments, demands and considerations

specifications, operational characteristics and process for identifying system components

typical problems, contingencies and solutions

applicable tools, equipment and testing devices and their operation

procedures for evacuating system

procedures for leak testing

procedures for adding refrigerant

requirements and procedures to isolate circuits/appliances

procedures for checking air flow

measuring instruments/equipment, specifications and procedures for checking temperature and system performance

measuring instruments/equipment, specifications and procedures for checking components

procedures for reporting non-conformances

process for identifying refrigerant type

types of commissiong documentation

requirements and procedures for completing documentation

OHS procedures and risk control measures

hazards and risk control measures associated with commissioning split and domestic air conditioning systems

Range Statement

The range statement relates to the unit of competency as a whole. It allows for different work environments and situations that may affect performance. Bold italicised wording, if used in the performance criteria, is detailed below. Essential operating conditions that may be present with training and assessment (depending on the work situation, needs of the candidate, accessibility of the item, and local industry and regional contexts) may also be included.

Tools, equipment and testing devices

Refrigeration gauge manifold, Schraeder access valves; quick connect couplings, thermometer/thermocouple temperature measuring devices; analogue and digital vacuum measuring gauges; digital scales; refrigerant recovery unit; vacuum pump; electronic leak detectors, refrigerant containers/cylinders

Legislative and industry requirements

Commonwealth, State and Territory legislation, regulations, standards and industry codes of practice

The Ozone Protection and Synthetic Greenhouse Gas Legislation Amendment Bill 2003; Air conditioning residential best practice guidelines (AIRAH); State and local building regulations

Sustainable environmental practices for commissioning and decommissioning split air conditioning and domestic refrigeration.

System performance

Pressure; temperature; sub cooling; superheating; evaporator coil to air temperature difference

Residential split air conditioning systems

Single head split systems up to 18kw cooling capacity

Domestic refrigeration and air conditioning systems

Domestic refrigeration and air conditioning systems being self contained 240 volt plug in self contained appliances primarily used in domestic/residential situations